Penguin

UPSMON

UPSMON

NAME SYNOPSIS DESCRIPTION OPTIONS UPS DEFINITIONS NOTIFY EVENTS NOTIFY COMMAND NOTIFY FLAGS NOTIFY MESSAGES POWER VALUES UPS TYPES TIMED SHUTDOWNS REDUNDANT POWER SUPPLIES MIXED OPERATIONS FORCED SHUTDOWNS DEAD UPSES RELOADING NUANCES SIMULATING POWER FAILURES FILES SEE ALSO


NAME

upsmon - UPS monitor and shutdown controller

SYNOPSIS

upsmon -h

upsmon -c command

__upsmon [-d? [-i? [-p? [-u__ ''user''?

DESCRIPTION

upsmon is the client process that is responsible for the most important part of UPS monitoring - shutting down the system when the power goes out. It can call out to other helper programs for notification purposes during power events.

upsmon can monitor multiple systems using a single process. Every UPS that is defined in the upsmon.conf(5) configuration file is assigned a power value and a type (slave or master).

OPTIONS

  • h

Display the help message.

  • c command

Send the command command to the existing upsmon process. Valid commands are:

fsd - shutdown all master UPSes (use with caution)

stop - stop monitoring and exit

reload - reread upsmon.conf(5) configuration file

  • d

Enable debugging mode. upsmon runs in the foreground and prints debugging information on stdout about the monitoring process.

  • i

Enable infinite loop at shutdown. upsmon will keep a process running after calling the shutdown command rather than exiting. This is only useful if you have shutdown scripts that complain when upsmon isn't running as they kill various processes.

  • p

Run privileged all the time. Normally upsmon will split into two processes. The majority of the code runs as an unprivileged user, and only a tiny stub runs as root. This switch will disable that mode, and run the old

  • u user

Set the user for the unprivileged monitoring process. This has no effect when using -p.

The default user is set at configure time with 'configure --with-user=...'. Typically this is 'nobody', but other distributions will probably have a specific 'nut' user for this task. If your notification scripts need to run as a specific user, set it here.

You can also set this in the upsmon.conf(5) file with the RUN_AS_USER directive.

UPS DEFINITIONS

In the upsmon.conf(5), you must specify at least one UPS that will be monitored. Use the MONITOR directive.

MONITOR system powervalue password type

The system refers to a upsd(8) server, in the form [[ __

Other possibilities include:

Finally, to use all of these options:

upsd__(8)? on port __

The powervalue refers to how many power supplies on this system are being driven this UPS. This is typically set to 1, but see the section on power values below.

Your password must match the entry in the upsd(8) server's upsd.conf(5) ACCESS directive for this system.

The type is either master or slave. In general, a master process is one running on the system with the UPS actually plugged into a serial port, and a slave is drawing power from the UPS but can't talk to it directly. See the section on UPS types for more.

NOTIFY EVENTS

upsmon senses several events as it monitors each UPS. They are called notify events as they can be used to tell the users and admins about the change in status. See the additional NOTIFY-related sections below for information on customizing the delivery of these messages.

ONLINE

The UPS is back on line.

ONBATT

The UPS is on battery.

LOWBATT

The UPS battery is low (as determined by the driver).

FSD

The UPS has been commanded into the

COMMOK

Communication with the UPS has been established.

COMMBAD

Communication with the UPS was just lost.

SHUTDOWN

The local system is being shut down.

REPLBATT

The UPS needs to have its battery replaced.

NOCOMM

The UPS can't be contacted for monitoring.

NOTIFY COMMAND

In upsmon.conf(5), you can configure a program called the NOTIFYCMD that will handle events that occur.

NOTIFYCMD path to program

NOTIFYCMD

Remember to wrap the path in

The program you run as your NOTIFYCMD can use the environment variables NOTIFYTYPE and UPSNAME to know what has happened and on which UPS. It also receives the notification message (see below) as the first (and only) argument, so you can deliver a preformatted message too.

Note that the NOTIFYCMD will only be called for a given event when you set the EXEC flag by using the notify flags, below:

NOTIFY FLAGS

By default, all notify events (see above) generate a global message (wall) to all users, plus they are logged via the syslog. You can change this with the NOTIFYFLAG directive in the configuration file:

NOTIFYFLAG notifytype flags

Examples:

NOTIFYFLAG ONLINE SYSLOG

NOTIFYFLAG ONBATT SYSLOG+WALL

NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC

The flags that can be set on a given notify event are:

SYSLOG

Write this message to the syslog.

WALL

Send this message to all users on the system via 'wall'.

EXEC

Execute the NOTIFYCMD.

IGNORE

Don't do anything. If you use this, don't use any of the other flags.

You can mix these flags.

NOTIFY MESSAGES

upsmon comes with default messages for each of the NOTIFY events. These can be changed with the NOTIFYMSG directive.

NOTIFYMSG type message''

Examples:

NOTIFYMSG ONLINE

NOTIFYMSG ONBATT

The first instance of %s is replaced with the identifier of the UPS that generated the event. These messages are used when sending walls to the users directly from upsmon, and are also passed to the NOTIFYCMD.

POWER VALUES

The

A

MONITOR upsname powervalue password type

Normally, you only have one power supply, so it will be set to 1.

MONITOR myups@myhost 1 mypassword master

On a large server with redundant power supplies, the power value for a UPS may be greater than 1. You may also have more than one of them defined.

MONITOR ups-alpha@myhost 2 mypassword master

MONITOR ups-beta@myhost 2 mypassword master

You can also set the power value for a UPS to 0 if it does not supply any power to that system. This is generally used when you want to use the upsmon notification features for a UPS even though it's not actually running the system that hosts upsmon. Don't set this to

MONITOR faraway@anotherbox 0 mypassword slave

The

MINSUPPLIES value

Typical PCs only have 1, so most users will leave this at the default.

MINSUPPLIES 1

If you have a server or similar system with redundant power, then this value will usually be set higher. One that requires three power supplies to be running at all times would simply set it to 3.

MINSUPPLIES 3

When the current overall power value drops below the minimum power value, upsmon starts the shutdown sequence. This design allows you to lose some of your power supplies in a redundant power environment without bringing down the entire system while still working properly for smaller systems.

UPS TYPES

Remember that upsmon and upsd(8) need not run on the same system. When they do, upsmon needs to monitor those UPSes as a master. This means that it will take charge of that UPS, and wait for all of the slaves to disconnect before shutting itself down. This synchronization ensures that systems that do monitoring over the network can shut down cleanly before the master's driver shutdown (-k) command turns them off.

When upsmon runs as a slave, it is relying on the distant system to tell it about the state of the UPS. When that UPS goes critical (on battery and low battery), it immediately invokes the local shutdown command. This needs to happen quickly. Once it disconnects from the distant upsd(8) server, the master upsmon will start its own shutdown process. Your slaves must all shut down before the master turns off the power or filesystem damage may result.

upsmon deals with slaves that get wedged, hang, or otherwise fail to disconnect from upsd(8) in a timely manner with the HOSTSYNC timer. During a shutdown situation, the master upsmon will give up after this interval and it will shut down anyway. This keeps the master from sitting there forever (which would endanger that host) if a slave should break somehow. This defaults to 15 seconds.

If your master system is shutting down too quickly, set the FINALDELAY interval to something greater than the default 15 seconds. At the same time, don't set this too high, or your UPS battery may run out of power before the master upsmon process shuts down that system.

TIMED SHUTDOWNS

For those rare situations where the shutdown process can't be completed between the time that low battery is signalled and the UPS actually powers off the load, use the upssched(8) helper program. You can use it along with upsmon to schedule a shutdown based on the __

This can be complicated and messy, so stick to the default critical UPS handling if you can.

REDUNDANT POWER SUPPLIES

If you have more than one power supply for redundant power, you may also have more than one UPS feeding your computer. upsmon can handle this. Be sure to set the UPS power values appropriately and the MINSUPPLIES value high enough so that it keeps running until it really does need to shut down.

For example, the HP !NetServer? LH4 by default has 3 power supplies installed, with one bay empty. It has two power cords, one per side of the box. This means that one power cord powers both power supply bays, and that you can only have two UPSes supplying power.

Connect UPS

When alpha goes on battery, your current overall power value will stay at 3, as it's still supplying power. However, once it goes critical (on battery and low battery), it will stop contributing to the current overall power value. That means the value will be 1 (beta alone), which is less than 2. That is insufficient to run the system, and upsmon will invoke the shutdown sequence.

However, if beta goes critical, subtracting its contribution will take the current overall value from 3 to 2. This is just high enough to satisfy the minimum, so the system will continue running as before. If beta returns later, it will be re-added and the current value will go back to 3. This allows you to swap out UPSes, change a power configuration, or whatever, as long as you maintain the minimum power value at all times.

MIXED OPERATIONS

Besides being able to monitor multiple UPSes, upsmon can also monitor them as different roles. If you have a system with multiple power supplies serviced by separate UPS batteries, it's possible to be a master on one and a slave on the other. This usually happens when you run out of serial ports and need to do the monitoring through another system nearby.

This is also complicated, especially when it comes time to power down a UPS that has gone critical but doesn't supply the local system. You can do this with some scripting magic in your notify command script, but it's beyond the scope of this manual.

FORCED SHUTDOWNS

When upsmon is forced to bring down the local system, it sets the

You can manually invoke this mode on the master upsmon by starting another copy with '-c fsd'. This is useful when you want to initiate a shutdown before the critical stage through some external means, such as upssched(8).

DEAD UPSES

In the event that upsmon can't reach upsd(8), it declares that UPS upsmon.conf(5). If this happens while that UPS was last known to be on battery, it is assumed to have gone critical and no longer contributes to the overall power value.

upsmon will alert you to a UPS that can't be contacted for monitoring with a

RELOADING NUANCES

upsmon usually gives up root powers for the process that does most of the work, including handling signals like SIGHUP to reload the configuration file. This means your upsmon.conf(8)? file must be readable by the non-root account that upsmon switches to.

If you want reloads to work, upsmon must run as some user that has permissions to read the configuration file. I recommend making a new user just for this purpose, as making the file readable by

See the RUN_AS_USER section in upsmon.conf(8)? for more on this topic.

SIMULATING POWER FAILURES

To test a synchronized shutdown without pulling the plug on your UPS(es), you need only set the forced shutdown (FSD) flag on them. You can do this by calling upsmon again to set the flag - i.e.:

upsmon -c fsd

After that, the master and the slaves will do their usual shutdown sequence as if the battery had gone critical. This is much easier on your UPS equipment, and it beats crawling under a desk to find the plug.

FILES

upsmon.conf(5)

SEE ALSO

Server:

upsd(8)

Clients:

upsc(8), upscmd(8), upsct(8), upsct2(8), upsmon(8)

Internet resources:

The NUT (Network UPS Tools) home page: http://www.exploits.org/nut/

NUT mailing list archives and information: http://lists.exploits.org/


This page is a man page (or other imported legacy content). We are unable to automatically determine the license status of this page.