13 !!NAME
14
15
16 upscmd - UPS administration program for instant commands
17 !!SYNOPSIS
18
19
20 __upscmd -h__
21
22
23 __upscmd -l__ ''ups''
24
25
26 __upscmd [[-u__ ''username''__] [[-p__
27 ''password''__]__ ''ups command''
28 !!DESCRIPTION
29
30
31 __upscmd__ allows you to invoke
32 __
33
34
35 On hardware that supports it, you can use this program to
36 start and stop battery tests, invoke a front panel test
37 (beep!), turn the load on or off, and more.
38 !!OPTIONS
39
40
41 -h
42
43
44 Display the help message.
45
46
47 -l ''ups''
48
49
50 Show the list of supported instant commands on that UPS.
51 Some hardware may not support any of them.
52
53
54 -u ''username''
55
56
57 Set the username for the connection to the server. This is
58 optional, and you will be prompted for this when invoking a
59 command if -u is not used.
60
61
62 -p ''password''
63
64
65 Set the password to authenticate to the server. This is also
66 optional like -u, and you will be prompted for it if
67 necessary.
68
69
70 ''ups''
71
72
73 Connect to that UPS. The format for this option is
74 [[upsname@]hostname[[:port].
75 !!UNATTENDED MODE
76
77
78 If you run this program inside a shell script or similar to
79 invoke a command, you will need to specify all of the
80 information on the command line. This means using -u and -p.
81 Otherwise it will put up a prompt and your program will
82 hang.
83
84
85 This is not necessary when displaying the list, as the
86 username and password are not required for read-only
87 mode.
88 !!DANGEROUS COMMANDS
89
90
91 Some drivers like apcsmart(8) have built-in paranoia
92 for the dangerous commands like OFF. To make them actually
93 turn off the load, you will have to send the command twice
94 within a short window. That is, you will have to send it
95 once, then send it again after 3 seconds elapse but before
96 15 seconds pass.
97
98
99 This paranoia is entirely defined within the driver. upsd
100 and upscmd have no control over the timing.
101 !!DIAGNOSTICS
102
103
104 upscmd won't work unless you provide a valid username and
105 password. If you get
106 upsd.users__(5) has an entry for you,
107 and that the username you are using has permissions to SET
108 variables.
109 !!BUGS
110
111
112 There is currently no way to tell the user when the driver
113 requires confirmation to invoke a command such as OFF.
114 Similarly, there is not yet a way to tell the user if a
115 command succeeds or fails.
116 !!SEE ALSO
117
118
2 perry 119 upsd(8), upsct2(8)
1 perry 120
121
122 __Internet resources:__
123
124
125 The NUT (Network UPS Tools) home page:
126 http://www.exploits.org/nut/
127